Voltiera
Power cable · NTP-IEC · SGS

Halogen-free LSOH-90+ cable, factory direct

LSOH-90+: 99.99% copper, 450/750V, 90°C, 1.5 to 300 mm² — for hospitals, schools, and public buildings.

  • SGS certified
  • Made in Peru
  • Full or mixed container
Specifications

LSOH-90+ cable at a glance

450/750 V
Voltage
90°C
Operating
1.5–300 mm²
16 sizes
NTP-IEC
SGS certified
Insulation
Thermoplastic LSOH (halogen-free)
Conductor
99.99% pure copper
Flame
Non-propagating per NTP-IEC 60332-3 Cat. C
Origin
Made in Peru
Packing
ReelsWooden drumsPallets

Ampacity in conduit

At 30°C ambient and 90°C conductor. Under each bar: ampacity in air and weight. Apply temperature and grouping correction factors.

SectionAmps in conduit
1.5 mm²
22A
In air 27 A · 20 kg/km
2.5 mm²
27A
In air 37 A · 30 kg/km
4 mm²
35A
In air 46 A · 45 kg/km
6 mm²
45A
In air 61 A · 65 kg/km
10 mm²
65A
In air 88 A · 105 kg/km
16 mm²
80A
In air 124 A · 160 kg/km
25 mm²
105A
In air 158 A · 255 kg/km
35 mm²
130A
In air 197 A · 345 kg/km
50 mm²
165A
In air 245 A · 475 kg/km
70 mm²
200A
In air 307 A · 670 kg/km
95 mm²
240A
In air 375 A · 925 kg/km
120 mm²
275A
In air 437 A · 1130 kg/km
150 mm²
315A
In air 501 A · 1435 kg/km
185 mm²
355A
In air 586 A · 1790 kg/km
240 mm²
415A
In air 654 A · 2340 kg/km
300 mm²
470A
In air 757 A · 2940 kg/km

Need pricing on LSOH-90+ cable?

Send us sections, quantities, and destination. We reply with a firm quote and incoterms.

Buying LSOH-90+ Cable Wholesale — FAQ

What is LSOH-90+ cable and why does "halogen-free" matter?

LSOH-90+ (Low Smoke Zero Halogen, 90°C rated) is a power cable with thermoplastic insulation that contains no halogens (no chlorine, fluorine, bromine, iodine). In a fire, halogenated insulation generates dense black smoke and toxic acid gas — both of which kill before flames reach occupants. LSOH-90+ generates no toxic gas and no dense smoke, which keeps egress paths visible. Required by code in hospitals, schools, public buildings, transit tunnels, and any installation where evacuation under fire is the design priority.

When do you specify LSOH instead of standard PVC cable?

When the building has fixed-population occupancy (hospitals, schools, prisons, airports), confined egress (tunnels, subway, underground transit), or institutional ownership where insurance and life-safety code drive the spec. Standard PVC and even low-halogen PVC (THW-90 BH) emit acid gas and smoke under fire — manageable in industrial buildings, lethal in dense-occupancy ones. The unit cost is higher than PVC; the project liability of using PVC where LSOH was specified is much higher.

What sections does Voltiera carry (1.5–300 mm²)?

All 16 standard sections: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, and 300 mm². Class 5 stranding above 6 mm². Sizes can mix in a single container without per-SKU minimum.

What is the ampacity by section?

Ampacity at 30°C ambient, 90°C conductor max. In open air: from 27 A at 1.5 mm² up to 757 A at 300 mm². In conduit (max 3 conductors): from 22 A at 1.5 mm² up to 470 A at 300 mm². Apply the temperature and grouping correction factors when 30°C ambient or 3 conductors per conduit are exceeded. Full table is in the section above.

Is the cable SGS-certified and NTP-IEC compliant?

Yes. NTP-IEC compliant, SGS-certified, manufactured in Peru with 99.99% pure copper conductor. Not "equivalent" — actual SGS certification, with the document delivered to the project on request.

Difference between LSOH-90+ and THW-90 BH?

LSOH-90+ is fully halogen-free with zero halogen content, no smoke, and no toxic gas — for hospitals, schools, public buildings. THW-90 BH is low-halogen-emission PVC: 40% lower smoke and 20% lower toxic gas than standard PVC, but not halogen-free. THW-90 BH is the cost-conscious choice for industrial, commercial, and warehouse environments where fire-egress density is lower. We carry both — choice depends on the project.

Does Voltiera export LSOH-90+ to Central America and the Caribbean?

Yes. Voltiera ships LSOH-90+ to specialty distributors, EPCs, and institutional projects across Central America (Guatemala, Honduras, El Salvador, Costa Rica, Panama), the Caribbean (Dominican Republic, Jamaica, Trinidad & Tobago), and South America (Colombia, Ecuador, Peru, Chile, Argentina). Full container or mixed with THW-90 BH, conduit, or other electrical materials.

What is the minimum order to buy LSOH-90+ wholesale by the container?

No fixed minimum. The honest question is whether the math works for a full container or whether a mixed container with THW-90 BH, conduit, or other electrical materials gets to a better landed cost. Send the sections and quantities by destination — we put together the configuration that gives the best total cost.

Request a Wholesale Quote